Automatic Phase Selector PEF-301
Product Details:
Brand | NOVATEK ELECTRO |
Voltage | 220 - 240 V AC |
Logic | Three phase input and single (best) phase output |
Current Rating (Amps) | 16 |
Usage/Application | Machine, Appliance, Industrial Control, Telecom, Cable TV networks |
Switch Type | Automatic Selector |
Model No. | PEF-301 |
PEF-301 universal automatic electronic phase switch is designed to supply industrial and household appliance single phase 220 - 230V/50Hz loads from three-phase four-wire mains 3x380+N with the purpose of maintaining uninterrupted power supply of essential single-phase loads and protect them against unallowable voltage variations in the mains.
Depending on voltage presence and voltage quality on phases, the PEF-301 will automatically select the optimal phase and promptly switch the single phase load supply of any wattage to this phase:
- Loads of wattage up to 3 kW (up to 16A) get power supply directly from PEF-301
- When wattage exceeds 3 kW (16A), PEF-301 phase switch will control the magnetic starters (MS) coils of corresponding wattage (MS can be supplied optionally)
Documentation for this device
Output Voltage:220 - 240 V AC
Application:Selection of best phase among 3 phase input, swichover to live phase in case of phase cut
Power Factor:1
Input Voltage:220 - 415 V AC
Additional Information:
- Item Code: PEF-301
- Port of Dispatch: New Delhi, India
TECHNICAL BRIEF
Nominal Phase Voltage, V |
220 - 240 |
Mains frequency, Hz |
45-55 |
Harmonical configuration (nonsinusoidality) of power supply voltage |
EN 61000-3-2 (IEC 1000-3-2) |
Trip threshold for Umin, V |
160-220 |
Trip threshold for Umax, V |
230-280 |
Adjustable reset delay, Ton, s |
1-600 |
Return delay range to the priority phase, Tr, (5—200), s |
present |
Return delay range to the priority phase, Tr, (200 -- ∞), s |
absent |
Fixed switch (de-energization) delay for Umin, s |
12 |
Switch delay to reserve phases, s, not more than |
0.2 |
Voltage hysteresis, V |
5 - 7 |
Accuracy, V |
±3 |
Maximum switched current of output contacts, Ð, no less than |
16 |
Operating phase voltage, V |
400 |
Transient withstand, V |
450 |
Power consumption (under load), W, not more than |
1.0 |
Protection class against electric shock |
II |
Permissible contamination level |
II |
Overvoltage category |
II |
Nominal impulse withstanding voltage, kV |
4 |
Nominal voltage of isolation, V |
450 |
Life of output contacts:
|
|
Cross section of wires of connection terminals, mm² |
0.5-2 |
Maximal tightening torque of terminals external screws, N*m |
0.4 |
Operating temperature, °C |
from -35 to +55 |
Weight, no more than, kg |
0.200 |
Mounting 35 mm DIN-rail |
|
Mounting position arbitrary |
PEF-301 complies with requirements:
IEC 60947-1:2004, ІDТ; ІEC 60947-6-2:1992, ІDT; CISPR 11:2004, IDT; IEC 61000-4-2:2001, IDT.