Automatic Phase selector PEF-320
The PEF-320 universal automatic electronic phase switch is designed to supply an industrial and domestic single phase 230 V, 50 Hz load from three-phase four-wire mains 3Ñ…400+N in order to maintain uninterrupted power supply of essential single-phase loads and protect them against unallowable voltage variations in the mains.
According to the voltage presence and voltage quality on the phases, the PEF-320 will automatically select the optimum phase in limits range set by user and switch the single phase load supply to this phase.
It is possible to connect to one of the phases of the electric generator, inverter.
The maximum and minimum voltage limits are set by user.
TECHNICAL BRIEF
Nominal Phase Voltage, V 220 - 240
Mains frequency, Hz 45-55
Harmonical configuration (nonsinusoidality) of power supply voltage EN 61000-3-2 (IEC 1000-3-2)
Trip threshold for Umin, V 170-220
Trip threshold for Umax, V 230-290
Adjustable reset delay, Ton, s 1-600
Return delay range to the priority phase, Tr, (5—200), s present
Return delay range to the priority phase, Tr, (200 -- ∞), s absent
Fixed switch (de-energization) delay for Umin, s 12
Switch delay to reserve phases, s, not more than 0.2
Voltage hysteresis, V 5 - 7
Accuracy, V ±3
Maximum switched current of output contacts, Ð, no more than 16
Operating phase voltage, V 400
Transient withstand, V 450
Power consumption (under load), W, not more than 1.0
Protection class against electric shock II
Permissible contamination level II
Overvoltage category II
Nominal impulse withstanding voltage, kV 4
Nominal voltage of isolation, V 450
Life of output contacts:
under load 16 A , operations, no less than 50 000
under load 5 A , operations, not more than 100 000
Cross section of wires of connection terminals, mm² 0.5-2
Maximal tightening torque of terminals external screws, N*m 0.4
Operating temperature, °C from -35 to +55
Weight, no more than, kg 0.150
Overall dimensions H*B*L, mm 90.2*36*64.5
Mounting 35 mm DIN-rail
Mounting position arbitrary
PEF-320 complies with requirements:
IEC 60947-1:2004, ІDТ; ІEC 60947-6-2:1992, ІDT; CISPR 11:2004, IDT; IEC 61000-4-2:2001, IDT.