Multifunction Programmable Timer REV-114
Product Details:
Display Type | Digital LED |
Model | REV-114 |
Brand | NOVATEK ELECTRO |
Application | On Delay, OFF Delay, Cyclic Timer, Pulse Generator, On/Off/Pulse after External Input |
The time delay relay REV-114 is the microprocessor-based device intended to control the load with independent time delay. It provides the certain sequence of the load operation according to the mode specified by the user.
REV-114 is equipped with control buttons and a digital display designed for adjustment and visual check of timing.
REV-114 can be operated by seventeen operation logics/algorithms:
- on-delay;
- time delay when energizing;
- periodic with on-delay;
- periodic with time delay when energizing;
- pulse generator;
- on-delay with external start;
- off delay with external start;
- pulse I with external start;
- pulse II with external start;
- on/off delay with external start;
- pitch of the load relay (during each control contact closing);
- periodic with external start and on-delay;
- periodic with external start and time delay when energizing;
- pulse generator with external start;
- start stop;
- always ON;
- always OFF.
Additional Information:
- Item Code: REV-114
- Port of Dispatch: New Delhi, India
Basic Specifications:
Description |
Value |
Operating supply voltage, V: |
230 / 240 |
Frequency of supply mains, Hz |
45 – 62 |
Voltage at which service capability is maintained, V |
185 – 280 |
Permissible harmonic configuration (un-sinusoidality) of power supply voltage |
EN 50160 |
Readiness time when energizing, s, no more than |
0.4 |
Accuracy of time setting holding, %, no less than |
0.5 |
Number of operation algorithms |
17 |
Adjustment range of time |
from 0.1 s to 10 days |
Timing adjustment |
Buttons on the front panel |
Digit display of remaining time |
available |
Service of the product |
Switchgear and control gear |
Rated operating condition |
Continuous |
Type and quantity of contacts (switching) |
2 |
Climatic design version |
NC 3.1 |
Protection rating of case |
ІР40 |
Protection rating of terminal box |
ІР20 |
Commutation lifetime of output contacts if cosj=1: - under load of 6 Ð, time, no less than - under load of 1 Ð, time, no less than |
100 000 1 000 000 |
Power consumption (under load), W, no more than |
0.5 |
Permissible contamination level |
II |
Overvoltage category |
II |
Electric shock protection class |
II |
Rated insulation voltage, V |
450 |
Rated impulse withstand voltage, kV |
2.5 |
Wire cross-section for connection to terminals, mm² |
0.5 – 2 |
Tightening torque of terminal screws, N*m |
0.4 |
Weight, kg, not more |
0.150 |
Overall dimensions, H x D x L, mm |
90 x 18 x 65 |
Product installation (mounting) is on standard 35mm DIN rail |
|
The product remains functional at any position in space |
|
Case material is self-extinguishing plastic |
Specifications of output contacts of the load relay:
Ños j |
Max. current at U~250 V, Ð |
Max. switching power, VA |
Max. permissible continuous AC voltage, V |
Max. current at UDC=28 V, A |
1 |
6 |
1500 |
250 |
3 |
REV-114 meets the requirements of the following:
IEC 60947-1 (Low-voltage switchgear; Part 1. General rules);
ІEC 60947-6-2 (Low-voltage circuit breaker and controller; Part 6-2; multifunctional equipment; Control and safety switching equipment);
CISPR 11 (Electromagnetic compatibility; Industrial, scientific and medical RF equipment; electromagnetic interference characteristics; standards and measuring procedure);
IEC 61000-4-2 (Electromagnetic compatibility; Part 4-2; Testing and measurement techniques; Electrostatic discharge immunity test).
Harmful substances in amounts exceeding maximum permissible concentrations are not available.