Power Limiting Relay OM-110
Product Details:
Voltage Type | AC |
Voltage (V) | 240 V |
Current (Amps) | 8A |
Number of Poles | 2 Pole |
Application | Power limitting relay, Power Display, Overload Relay |
OM-110 power limiting relay is used for continuous control of single phase active or total power. The measured power range is between 0 and 20 kW or between 0 and 20 kVA OM-110 rejects the load in case the user-set maximum allowed load consumption power level is exceeded (with a set rejection time), and subsequently activates the load automatically (with a set activation delay time, or an option to block reclosing).
Potentiometers and DIP-switches installed in the front panel allow the user to set the following values:
- Maximum allowed power level
- Relay activation time
- Automatic reclosing delay time
The load consumption is measured without electrical opening, using an integrated current sensor.
OM-110 relay can be used in the following capacities:
- Digital wattmeter (active or full power meter)
- Load consumption limiting relay
- OM-110 is powered by the voltage measuring circuits
Documentation for this device
Additional Information:
- Item Code: OM-110
- Port of Dispatch: New Delhi, India
Technical Specifications:
Purpose of device |
Control and distribution equipment. |
|
|
Rated power supply voltage, V |
230/240 |
|
|
Typical operation |
Continued |
|
|
Rated voltage frequency, Hz |
47– 53 |
|
|
Harmonical configuration (nonsinusoidality) of power supply voltage |
EN 61000-3-2 (IEC 1000-3-2) |
|
|
Measurement range of power, , kW (kVA) |
0– 20,0 |
|
|
Power measurement accuracy is not less than |
2.5% |
|
|
Adjustable range for setting maximal power a) k=1; Wmax, kW( kVA) Absolute deviation for power measurement not more than, kW (kVA) b) k=10; Wmax, kW(kVA) Absolute deviation for current measurement not more than, kW, kVA |
0– 1.075 ±0,05 0– 20 ±0,5 |
|
|
Adjustable time range for autoreclosing time delay - ton, sec |
0– 900, ∞ |
|
|
Adjustable time range for tripping time delay – toff, sec |
0– 300 |
|
|
Readiness time after turn ON, not more than, sec* |
0,8 |
|
|
Maximal commutation current on the output terminals, Ð, not less |
8 |
|
|
Minimum voltage when safe operating (effective value), V ** |
130 |
|
|
Maximal voltage when safe operating (effective value), V |
300 |
|
|
|
Maximum permissible voltage, V, |
400 |
|
Protection degree: - device - terminal block |
IP40 IP10 |
|
|
Index protection of electrical shock |
II |
|
|
Permissible degree of pollution |
II |
|
|
Overvoltage category |
II |
|
|
Nominal voltage of insulation, V |
450 |
|
|
Rated impulse withstand voltage, kV |
2.5 |
|
|
Power consumption (when load is disconnected), kW |
to 3.5 |
|
|
Commutation lifetime for the output contacts: - under the load of 8Ð, not less than - under the load of 1A, not less than |
100 000 1 000 000 |
|
|
Torque for terminal screws, N*m |
0.4 |
|
|
Weight, kg, not more than |
0.200 |
|
|
Dimensions (3 way standard DIN module thickness for DIN rail mounting), mm |
90 Ñ… 52,6 Ñ… 69,1 |
|
|
Positioning - free |
|
|
|
The wire cross section of connecting terminals is 0.5 - 2.0 mm2 |
|
|
|
Mounting to standard 35 mm DIN-rail |
|
|
|
*In the extreme right position of the knob, turn-off time of 295 s is allowed. **Reaction time on turn ON is not more than 2 seconds. This time includes device selftesting, turning ON the power load, measuring power consumption and tripping the power load OFF in case fault situation is detected. *** To increase operational range to low voltage ОМ-110 has function to disable LED digital indicator if voltage level gets lower than 130V. If voltage level is less than 110V then OM-110 automatically opens its output terminals to initial cold state position and thus tunrs OFF. |
|
OM-110 complies with requirements IEC 60947-1, ІEC 60947-6-2, CISPR 11, IEC 61000-4-2.
Harmful substances in concentration more than allowed are absent.