Programmable Astro Timer With Photo Sensor REV-302
Product Details:
Brand | NOVATEK ELECTRO |
Display Type | Digital |
Model | REV-302 |
Current | 16A per Channel |
Voltage | 230V AC & 24V DC |
Channels | 2 Channel, independent operation |
Power/Voltage (V) | 3.5 kW per channel |
Display | Graphic LCD, Digital |
Usage/Application | Astronomical Time Switch, Lighting System Smart Control, Street Light Automation, Indoor and Outdoor Lightng Automation, Machine/Equipment On/Off operation |
Model No. | REV-302 |
Programmable Astronomical Timer With Photo Sensor and Voltage Protection.
REV-302 multifunctional relay is a microprocessor based programmable device designed to energize/de-energize one or two loads within user set time intervals based on astronomical logic, yearly timer, weekly timer, daily timer, simple timer logics, circuit voltage (over & under voltage) and external photo sensor (illumination intensity) basis.
Specific features of REV-302:
- Two potential free switching contact groups (two channels) of 16A @ 250V AC rated current
- Power supply: 90 - 420V 50/60Hz AC, 100 - 300V DC or 8 - 30V DC battery
- Time relay, voltage relay and photo relay combined or independent operation
- Flexible contact switching control transfer between the voltage relay, the photo relay and time relay
- 8 independent control programs and capability of swift transfer between them for each contact group
- Common internal memory for 5000 independent events distributed between all programs for day/week/month/year mode depending on the mode selected
- Option of controlling both terminal groups with a single program or independently with two seperate programs
- 10 year calendar (RTC) standalone power supply
- Astronomical, Daily, weekly, monthly, and yearly time relay program
- Independent timers settings lists for each program
- Planned event clock accuracy of up to 1 second
- Option for programmable holiday and day off list
- Specific timer list execution for days off and holidays
- Common built-in memory for 5000 independent timers distributed between all programs for day/week/month/year mode depending on the mode selected
- Option of program cyclic repeat within a specified time interval
- Automatic summer/winter time conversion
- Pulse time relay function (periodic, calendar independent contacts close/open)
- Function of plain contacts closure within a specified delay after energization
- Contacts close/open based on minimum and maximum circuit voltage
- Temporary delay for the after-energization relay start
- Separate time delays for the voltage relay and the photo relay actions (for setting the reclosing time, etc.)
- External photo sensor
- LCD graphical display
- Each channel status indication
- PC connection USB interface
- PC software with convenient graphical interface allowing to edit all relay settings and to create event arrays, or sunrise and sunset activated events
- Multiple language interface
- Menu control via 5 keys on the front panel
- Loading preset control programs via USB with use of supplemental software
- Password protection option for the settings menu
- Common reset key on the front panel
Additional Information:
- Item Code: REV-302
- Port of Dispatch: New Delhi, India
Technical parameters:
AC voltage (terminals 7-8), V |
90 ÷ 420 |
DC voltage (terminals 7-8), V |
100 ÷ 300 |
Rated DC battery voltage (terminals 9-10), V, optional |
8 ÷ 30 |
Supply curcuit frequency range, Hz |
50/60 |
Internal fuse |
available |
Max number of events |
5000 |
Clock error, sec/day, sec, not more then |
1 |
Clock standalone operation, when de-energized, years, no less than |
10 |
Setting accuracy, sec |
1 |
Voltage tripping threshold setting accuracy, V |
1 |
Voltage measurement error, %, not more then |
2 |
Illumination intensity measurement error up to 200 lx, %, not more then |
10 |
Illumination intensity measurement error over 200 lx, %, not more then |
20 |
Minimum time for the time relay contacts switching, sec |
0,015 |
Minimum time for the voltage relay contacts switching, sec |
0,035 |
Minimum time for the photo relay contacts switching, sec |
0,1 |
Voltage lower tripping threshold setting range, Umin,V |
90-416, but not more then Umax–dUmax |
Voltage upper tripping threshold setting range, Umax,V |
94-420, but no less than Umin+dUmin |
Min voltage threshold hysteresis dUmin, V |
3 ÷ 9 |
Max voltage threshold hysteresis dUmax, V |
3 ÷ 9 |
Tripping delay for Umin |
from 0 sec to 19 min 59 sec |
De-energize tripping delay for Umax* |
from 0 sec to 19 min 59 sec |
Load re-energization delay |
from 1 sec to 19 min 59 sec |
Illumination level settings range, lux |
0 ÷ 9999 |
Illumination level settings hysteresis, lux |
0 ÷ 999 |
Action delay if illumination is lower than the threshold value |
from 0 sec to 99 min 59 sec |
Action delay if illumination is higher than the threshold value |
from 0 sec to 99 min 59 sec |
General delay after re-energization |
from 0 sec to 99 min 59 sec |
Load relay trip indication |
available |
Settings backup in case of circuit and standalone power supply failure |
available |
Data memory, years, no less than |
10 |
Computer connection |
USB |
Photo sensor cable length, m |
2 |
Distance between the device and the photo sensor, m, not more then |
20 |
Event log |
year / month / week / day |
Allowable humidity without condensate, % |
90 |
Protection degree: |
ІР20 |
Power consumption (under load), VA, not more then |
3,0 |
Weight, kg, not more then |
0,150 |
Dimensions, mm |
90 Ñ… 52 Ñ… 66 |
Operating temperature range, °C |
from -20 to +55 |
Storage temperature, °C |
from -35 to +70 |
Quantity of output relays (channels) |
2 |
Number and type of contacts per channel (changeover contacts) |
1P |
Mounting: |
standard 35 mm DIN-rail |
Mounting position: |
Any |
* For fastest opening it is recommended to leave the parameter at «00 min 00 sec» value. |
Output contacts specification:
Ños j |
Max. current at |
Maximum power |
Max. current at |
1,0 |
16 Ð |
4000 VÐ |
16 Ð |
0,4 |
4 A |
1000 VÐ |
|
|
|
||
Output contacts commutation lifetime: - mechanical life (times) - electrical life 10Ð, 250V AC, times, no less than - electrical life 10Ð, 24V DC, times, no less than - electrical life 4Ð, 250V AC, (Ños j = 0,4 ), times, no less than |
107 100 thousand 30 thousand 100 thousand |
REV-302 complies with requirements:
IEC 60947-1:2004, ІDТ; ІEC 60947-6-2:1992, ІDT; CISPR 11:2004, IDT; IEC 61000-4-2:2001, IDT
No harmful substances in excess of the maximum permissible concentration is available.