Single Phase Voltage Monitor Relay RN-102
Product Details:
Minimum Order Quantity | 3 Piece |
Voltage Type | AC |
Voltage (V) | 220 - 240V AC |
Number of Poles | 2 Pole |
Current (Amps) | 32A |
Application | Single phase voltage monitoring |
The RN-102 voltage monitoring relay is designed to de-energize an industrial/appliance single-phase 220V/50Hz load in case of inadmissible voltage variations in the mains with subsequent automatic re-energizing after the circuit parameters recovery. Load is connected to the relay either directly via relay terminals or through a magnetic starter, depending on the wattage.
The relay can operate in four independent modes:
- Voltage monitoring relay
- Minimum voltage monitoring relay
- Maximum voltage monitoring relay
- Time relay with a restart delay
The device front panel features load status indicator (on/off) and three-digit, seven-segment display, which displays (depending on the device status):
- Actual RMS voltage
- Accurate value of the set-up parameter
- Time remaining till automatic load re-energizing
- Emergency de-energizing the load (RMS voltage flashing)
The variable pot knobs on the front panel allow for setting:
- The maximum allowable voltage tripping threshold
- The minimum allowable voltage tripping threshold
- Time delay for load re-energizing after the circuit parameters recovery
The RN-102 equipment includes a surge protector which protects the switched load against high frequency and high voltage impulse interference.
Documentation for this device
Additional Information:
- Item Code: RN-102
- Port of Dispatch: New Delhi
TECHNICAL CHARACTERISTICS
Rated voltage, V |
240 |
Rated voltage frequency, Hz |
47 – 65 |
Harmonical configuration (non-sinusoidality) of power supply voltage |
EN 61000-3-2 (IEC 1000-3-2) |
Adjustable settings ranges: - Minimal voltage tripping threshold (Umin), V - Maximal voltage tripping threshold (Umax), V - Auto-reclosing time delay, sec |
180 – 240 250 – 300 5 –900 |
Device level protection |
IP30 |
Fixed tripping time delay when input voltage exceeds the minimal tripping threshold (Umin), sec |
7 |
Fixed tripping time delay when input voltage exceeds the maximal tripping threshold (Umax), sec |
1 |
Fixed tripping time delay in case of voltage decrease more than 60V than the adjusted minimal voltage tripping threshold (Umin), sec |
0.12 |
Fixed tripping time delay in case of voltage increase more than 30V than the adjusted maximal voltage tripping threshold (Umax), sec |
0.12 |
Maximal commutation current (active power load), A (not less than) AC-1 type |
32 |
Accuracy for tripping basing the voltage level measurement, V |
< 3 |
Minimal operation voltage level at which PH-102 will keep working, V Maximal operation voltage level at which PH-102 will keep working, V |
120 400 |
Voltage hysteresis, V |
4 |
Protection class against electric shock |
II |
Overvoltage category |
II |
Permissible contamination level |
II |
Nominal voltage of isolation, V |
450 |
Rated impulse withstand voltage, kV |
2.5 |
Guide section of connecting plugs, mm2 |
0.3-3.3 |
Maximum moment of an inhaling of screws of connection terminal, N*m |
1.2 |
Operational temperature range, °Ð¡ |
from -30 to + 55 |
Total power consumption, mA |
< 15 |
Commutation lifetime of the output contacts: - under 32A power load, times (not less than) - under 5A power load, times (not less than) |
100 000 1 000 000 |
Outer dimensions, mm |
80 Ñ… 120 Ñ… 43 |
Net weight, kg |
0.250 |
Wall mounting in vertical position in order to read the digits of the front panel indicator |