Single Phase Voltage Monitor Relay RN-111M
Product Details:
Voltage Type | AC |
Voltage (V) | 220 - 240 V |
Number of Poles | 2 Pole |
Application | Industrial & domestic equipment/load protection, Neutral break protection |
Current (Amps) | 16A @ 250 V AC Max (upto 3.5 kW) |
The RN-111M voltage monitoring relay is designed to de-energize an industrial/appliance single phase 220 - 240V/50Hz load in case of inadmissible voltage variations in the mains with subsequent automatic re-energizing after the circuit parameters recovery. Load is connected to the relay either directly via relay terminals or through a magnetic contactor, depending on the wattage.
The relay can operate in four independent modes:
- Maximum and Minimum Voltage monitoring relay
- Minimum voltage monitoring relay
- Maximum voltage monitoring relay
- Time relay with a restart delay
The device front panel features load status indicator (on/off) and three-digit, seven-segment display, which displays (depending on the device status):
- Actual RMS voltage
- Accurate value of the set-up parameter
- Time remaining till automatic load re-energizing
- Emergency de-energizing the load (RMS voltage flashing)
The variable pot knobs on the front panel allow for setting:
- The maximum allowable voltage tripping threshold
- The minimum allowable voltage tripping threshold
- Time delay for load re-energizing after the circuit parameters recoveryest
Additional Information:
- Item Code: RN-111M
- Port of Dispatch: New Delhi, India
Main Technical Specifications
Rated voltage, V |
220-240 |
Rated voltage frequency, Hz |
47 – 65 |
Harmonical configuration (nonsinusoidality) of power supply voltage |
EN 50160 |
Adjustment ranges: - minimal voltage tripping range (Umin), V - maximal voltage tripping range (Umax), V - autoreclosing time delay (Ton), sec |
160 – 230 240 – 280 5 –900 |
Fixed tripping time delay in case maximal voltage fault (Umax) detected, sec |
1 |
Fixed tripping time delay in case minimal voltage fault (Umin) detected, sec |
12 |
Fixed tripping time delay in case of voltage decrease more than 60V than the adjusted minimal voltage tripping threshold (Umin), sec |
0.2 |
Fixed tripping time delay in case of voltage increase more than 30V than the adjusted maximal voltage tripping threshold (Umax), sec |
0.12 |
Maximal commutation current (active power load), A |
16 |
Tripping Voltage level accuracy, V |
up to 3 |
Minimal operation voltage level at which RN-111M will keep working, V |
100 |
Maximal operation voltage level at which RN-111M will keep working, V |
420 |
Voltage hysteresis, V |
4 - 5 |
Rower consumption (when de-energization load), W |
to 3.5 |
Commutation life of the output contacts: - under 16A power load, times (no less than) - under 5A power load, times (no less than) |
100 000 1 000 000 |
Outer dimensions, (2 S-modules), |
Fiqure 1 |
Weight, kg, no less than |
0.10 |
Casing material – self-extinguishing plastic |
|
The device preserves functionality in any position within the space |
Parameters of the integrated relay output terminals
|
Maximal current at ~ 250V AC |
Maximal power when contacts are closed |
Maximal commutation power |
Maximal allowed AC/DC Voltage |
Maximal current at 30V DC |
Cos j = 0.4 Cos j = 1 |
5 Ð 16A |
5000 VA |
4000 VA |
380/150 V |
5 Ð |
No harmful substances in excess of the maximum permissible concentration is available.
RN-111M complies with requirements:
IEC 60947-1:2004; ІEC 60947-6-2:1992; CISPR 11:2004; IEC 61000-4-2:2001.