Three Phase Voltage Monitor Relay RNPP-311M
Product Details:
Voltage Type | AC |
Voltage (V) | 400 - 415 V |
Number of Poles | 3 Pole, 4 Pole |
Application | Three phase voltage monitoring relay, Protection of three phase load |
Current (Amps) | 5A @ 250 V AC |
Brand | NOVATEK ELECTRO |
Contact Form | DPDT |
Type | Overvoltage Relay, Undervoltage relay, Voltage Imbalance, Phase Loss, Phase Sequence, Shorting of Phases protection |
RNPP-311M voltage monitoring relay is designed for protection of three phase loads against major types of mains faults, such as:
- RMS voltage reaching beyond admissible thresholds - over and under voltage
- Phase loss or Single phasing
- Phase sequence order violation or reverse phase sequence
- Phase coincidence or shorting of two or more phases
- Phase Imbalance or asymmetry
The device performs monitoring of the main circuit parameters and de-energizes (trip) load when the parameters fall beyond specified boundaries.
The front panel LEDs display the following:
- Presence of true RMS voltage in the mains
- Load status (On/Off)
- Type of fault
Adjustment potentiometers allow for setting:
- Tripping threshold for the minimum/the maximum voltage, (% of the rated voltage)
- Time delay for load re-energizing (reset) after the circuit parameters recovery
- Tripping time delay for load de-energizing (trip) in case of all circuit voltage faults
With DIP switches on the device’s front panel the user can select the type of circuit monitored 400 / 415V, and turn on/off monitoring of the following circuit parameters:
- Phase sequence
- Phase imbalance or asymmetry
- Under voltage
- Over voltage
Corresponding combinations of the RNPP-311M switches allow for functioning in various modes:
- Mode of circuit voltage comprehensive monitoring
- Minimum/the maximum voltage monitoring mode
- Minimum voltage monitoring mode
- Maximum voltage monitoring mode
- Phase presence monitoring mode
- Phase sequence violation and phase coincidence monitoring mode
- Phase imbalance monitoring mode; and other modes
The phase availability monitoring function is maintained in any position of the switches, including OFF position. The feature of 24V DC online power supply is available (optional).
Documentation for this device
Additional Information:
- Item Code: RNPP-311M
- Port of Dispatch: New Delhi, India
Technical Specification:
Rated line/phase voltage, V
|
400/230, 415/240 |
Rated frequency, Hz |
45 - 65 |
Harmonical configuration (non-sinusoidality) of power supply voltage |
EN 61000-3-2 (IEC 1000-3-2) |
Adjustable range for Umax/Umin, % of nominal value Unom |
5 - 50 |
Adjustable Tripping time delay (Toff), sec |
0 - 10 |
Adjustable Auto-reset time delay (Ton), sec |
0 - 600 |
Fixed time delay for tripping in case MIN voltage fault detected (time delay for Umin), sec |
12* |
Reaction time in case of phase loss, sec (not more) |
0,2 |
Readiness time on energizing the RNPP-311M, sec (not more) |
0,2** |
Phase imbalance value, V |
60 |
Voltage hysteresis, V |
5 - 6 |
Phase imbalance hysteresis, V |
5 - 6 |
Accuracy for voltage tripping threshold measurement, V (not more) |
3 |
Accuracy for phase imbalance measurement, % (not more) |
2 |
Protection class against electric shock |
II |
Permissible contamination level |
II |
Overvoltage category |
II |
Nominal voltage of isolation, V |
450 |
Operational voltage range, % of rated voltage |
from 50 to 150 |
Rated impulse withstand voltage, kV |
2.5 |
Power consumption (under power load), VA (not more) |
3.0 |
Maximal current that output contacts may commutate, A |
5 |
Cross-section area of connection terminals, mm² |
0.5 – 2 |
Maximum torque of terminal fixing, N*m |
0.4 |
Commutation endurance for the output contacts: - under 5Ð power load, not less than - under 1Ð power load, not less than |
100000times 1000000times |
Protection degree: - for the device - for the terminals |
IP40 IP20 |
Operational temperature range, °Ð¡ |
from - 35 to +55 |
Storage temperature conditions, °Ð¡ |
from - 45 to +60 |
Weight, kg (not more) |
0.200 |
Standard 35 mm DIN rail mounting |
|
Mounting position as per requirement (arbitrary) |
Specification of the Output contacts (1-2-3 and 4-5-6)
Cos j |
Maximal current at ~ 250V |
Maximal capacity |
Maximal AC Voltage |
Maximal current at 30V DC |
0,4 1,0 |
5 A 2 Ð |
1250 VA 500 VA |
400 V |
3 Ð |