Three Phase Voltage Monitor Relay RNPP-311M

Three Phase Voltage Monitor Relay RNPP-311M

Product Details:

Voltage Type AC
Voltage (V) 400 - 415 V
Number of Poles 3 Pole, 4 Pole
Application Three phase voltage monitoring relay, Protection of three phase load
Current (Amps) 5A @ 250 V AC
Brand NOVATEK ELECTRO
Contact Form DPDT
Type Overvoltage Relay, Undervoltage relay, Voltage Imbalance, Phase Loss, Phase Sequence, Shorting of Phases protection 

RNPP-311M voltage monitoring relay is designed for protection of three phase loads against major types of mains faults, such as:

  • RMS voltage reaching beyond admissible thresholds - over and under voltage
  • Phase loss or Single phasing
  • Phase sequence order violation or reverse phase sequence
  • Phase coincidence or shorting of two or more phases
  • Phase Imbalance or asymmetry

The device performs monitoring of the main circuit parameters and de-energizes (trip) load when the parameters fall beyond specified boundaries.

The front panel LEDs display the following:

  • Presence of true RMS voltage in the mains
  • Load status (On/Off)
  • Type of fault

Adjustment potentiometers allow for setting:

  • Tripping threshold for the minimum/the maximum voltage, (% of the rated voltage)
  • Time delay for load re-energizing (reset) after the circuit parameters recovery
  • Tripping time delay for load de-energizing (trip) in case of all circuit voltage faults

With DIP switches on the device’s front panel the user can select the type of circuit monitored 400 / 415V, and turn on/off monitoring of the following circuit parameters:

  • Phase sequence
  • Phase imbalance or asymmetry
  • Under voltage
  • Over voltage

Corresponding combinations of the RNPP-311M switches allow for functioning in various modes:

  • Mode of circuit voltage comprehensive monitoring
  • Minimum/the maximum voltage monitoring mode
  • Minimum voltage monitoring mode
  • Maximum voltage monitoring mode
  • Phase presence monitoring mode
  • Phase sequence violation and phase coincidence monitoring mode
  • Phase imbalance monitoring mode; and other modes

The phase availability monitoring function is maintained in any position of the switches, including OFF position. The feature of 24V DC online power supply is available (optional).

Documentation for this device

Additional Information:

  • Item Code: RNPP-311M
  • Port of Dispatch: New Delhi, India

Technical Specification:

Rated line/phase voltage, V

 

400/230,

415/240

Rated frequency, Hz

45 - 65

Harmonical configuration (non-sinusoidality) of power supply voltage

EN 61000-3-2 (IEC 1000-3-2)

Adjustable range for Umax/Umin, % of nominal value Unom

5 - 50

Adjustable Tripping time delay (Toff), sec

0 - 10

Adjustable Auto-reset time delay (Ton), sec

0 - 600

Fixed time delay for tripping in case MIN voltage fault detected (time delay for Umin), sec

12*

Reaction time in case of phase loss, sec (not more)                

0,2

Readiness time on energizing the RNPP-311M, sec (not more)

0,2**

Phase imbalance value, V

60

Voltage hysteresis, V

5 - 6

Phase imbalance hysteresis, V

5 - 6

Accuracy for voltage tripping threshold measurement, V (not more)

3

Accuracy for phase imbalance measurement, %  (not more)

2

Protection class against electric shock

 II

Permissible contamination level

 II

Overvoltage category

 II

Nominal voltage of isolation, V

 450

Operational voltage range, % of rated voltage

from 50 to 150

Rated impulse withstand voltage, kV

2.5

Power consumption (under power load), VA (not more)

3.0

Maximal current that output contacts may commutate, A

5

Cross-section area of connection terminals, mm²

0.5 – 2

Maximum torque of terminal fixing, N*m

0.4

Commutation endurance for the output contacts:

   - under 5А power load, not less than

   - under 1А power load, not less than

                       100000times

1000000times

Protection degree:

  - for the device

  - for the terminals

 

IP40

IP20

Operational temperature range, °Ð¡

from - 35 to +55

Storage temperature conditions, °Ð¡

from - 45 to +60

Weight, kg (not more)

0.200

Standard 35 mm DIN rail mounting

 

Mounting position as per requirement (arbitrary)

Specification of the Output contacts (1-2-3 and 4-5-6)

Cos j 

Maximal current at ~ 250V

Maximal capacity

Maximal AC Voltage

Maximal current

at 30V DC

0,4

1,0

5 A

2 А 

1250 VA

500 VA

400 V

3 А

RNPP-311M complies with requirements IEC 60947-1:2004, ІDТ, ІEC 60947-6-2:1992, ІDT, CISPR 11:2004, IDT, IEC 61000-4-2:2001, IDT.